The MIT200 installation tester provides technicians the tools for preforming insulation and continuity testing. Its unique display offers a combination of a digital and analog readouts, using Megger’s DART display technology. This combination offers a clear and easy-to-read display which allows for measurement data to be read accurately and with confidence. The analog pointer response allows uses to evaluate circuit charge and discharge characteristics. The ABS housing is constructed to withstand rigorous use for a long service life, while its small size fits into the user’s pocket for maximum portability.
规格:
Weight:
1.2 lb (550g)
Dimensions:
7.7 x 3.9 x 1.6 in. (195 x 98 x 40 mm)
Insulation Ranges
Nominal test voltage:
500 VDC
Measuring range:
10 kΩ - 1000 MΩ
Terminal voltage on open circuit DC:
-0% +25% of rated voltage
Short circuit current:
205 mA +10 mA –5 mA
Test current on load:
>1 mA at minimum pass values of insulation as specified in BS7671, HD384, IEC364 and VDE0413 part 1
Continuity Ranges
Measuring range:
0,01Ω - 100,0 Ω
(0 -50 Ω on analogue scale) Open circuit voltage: 5 V ±1 V
Short circuit current:
205 mA, ±5mA (0-10 Ω) >20 mA (0 - 100 Ω) Ω
特征:
Display of insulation measurement up to 1000 MΩ
Continuity range with 0,01 Ω resolution
Short circuit current in excess of 200 mA
Combined analogue arc and digital display
Automatic continuity testing
Automatic power-down when left unattended
Automatic voltage detection and warning
Test lead zero allows compensation for test lead resistance up
to 10 Ω
Meets the international requirements of EN 61557 for
Insulation and Continuity testing
Includes test leads and tough carry case